[email protected]D-100-P1 Flow Display Manual 05/14 - 0660-3 / 18343 Page 14
1.8.2 D-100-P1 Point Database
P1 POINTS
Pt Name/Range Type Category COV OVR Default Initial Current
1 Address Range: 1-99 02 LAO NO YES 99 11
H
None
2 Application 02 LAO NO NO 1999
10
1999
10
None
4 Flow Rate - 0-32,767 03 LAI YES NO 0 0 Integer
5 Ai3 - Generic Analog Input 1 03 LAI YES NO 0 0 Integer
6 Ai4 - Generic Analog Input 2 03 LAI YES NO 0 0 Integer
8 Operating Mode: 1/Forward, 2/Reverse 03 LDI NO NO 0 0 Byte
11 W0-M1Volume: 000,000-009,999 03 LAI NO NO 0 0 Integer
12 W1-M1 Volume: 010,000-999,999 03 LAI NO NO 0 0 Integer
15 W0-M2 Volume: 000,000-009,999 03 LAI NO NO 0 0 Integer
16 W1-M2 Volume: 010,000-999,999 03 LAI NO NO 0 0 Integer
17 W0-AuxiIn-1: 000,000-009,999 03 LAI NO NO 0 0 Integer
18 W1-AuxiIn-2: 010,000-999,999 03 LAI NO NO 0 0 Integer
19 Not Used
20 Point 20, Override Time (Hours)
Range 0-FF
02 LAO NO YES 1 1 None
22 M-1 V Reset - 0/Off, 1/Reset 01 LDO NO YES 0 0 Byte
24 M-2 V Reset - 0/Off, 1/Reset 01 LDO NO YES 0 0 Byte
25 AuxIn Reset - 0/Off, 1/Reset 01 LDO NO YES 0 0 Byte
29 DAY.NGT
ON=Night; OFF=Day; Default=OFF
01 LDO NO YES 0 0 Byte
99 ERROR STATUS Bit Oriented 01 LAO NO YES 0 0 Integer
100 Point 100
Factory Flag
Factory Flag is not a point in the sense that the others are. It is referenced only
by the Memorize Point Command. Other commands should NAK it with “POINT
DOES NOT EXIST”.
NOTE: Also refer to the Siemens’ Application Note, Document No. XXX for additional information.