1.5 BACnet MS/TP BAUD RATE, BIASING & TERMINATION
1.5.1 Baud Rate
Every ONICON Btu meter is individually programmed at the factory with application
specic data provided by the customer during the process of ordering the meter, and this
normally includes the Baud rate setting. If the Baud rate was provided, the meter will be
congured to operate at the specied rate. The standard Baud rate settings are 9600,
19200, 38400 and 76800 Baud.
If the Baud rate setting was not provided to ONICON, the System-10 will be congured to
“auto” detect the Baud rate of the network. In this conguration, the meter should detect
and automatically adjust to the proper rate when it is connected to the network.
The Baud rate setting can be manually changed in the eld. The photos and table below
show the Baud rate dipswitch settings.
B1 B2 B3 B4 Rate
0 0 0 0 Autobaud
1 0 0 0 9600
0 1 0 0 19200
0 0 1 0 38400
0 0 0 1 76800
Baud Rate Dip Switches