System-10 BTU Meter Manual 03/15 - 0651-16 / 18323 Page 24
3.3.5 Isolated Analog Output(s) (Optional):
The System-10 can be congured to provide up to four isolated analog outputs of the
following ve parameters: supply temperature, return temperature, ow rate, Btu rate and
delta temperature. The output type, 4-20 mA, 0-10 VDC or 5 VDC is eld congurable. The
selected outputs and associated scaling are congured at the factory. See the certicate of
calibration or label located on the inside cover for analog output conguration information.
Please note: If System-10 is ordered with a ow meter capable of producing an analog
output, the output signal will be available at terminal T5.
J1
5
G
60HZ
1
J2-1
+15
+24
J2-12
G
G
10
R7
H3
R1
20075-50 REV. A
LED1
T1
D1
D2
VAR1
F1
1/4 AMP
TB1
D4
D3
H1
1
L1 N Not Used
!
CAUTION
Analog outputs are all congured as active outputs. Do not apply power to any of the 4-20mA,
0-10 or 0-5 volt outputs. Doing so will damage the output.