[email protected]System-10 Dual Network Interface Installation Guide 05/14 - 0972-1 Page 24
REGISTER
ADDRESS
DESCRIPTION
REGISTER
RANGE
DATA
RANGE
OVER
RANGE
READ/
WRITE
COMMENT
40032 Energy Total Mode 1 – TonHr 0 – 65535 0 – 999 Read Only Low Order
40033 Energy Total Mode 1 – kTonHr 0 – 65535 0 – 65534 65535 Read Only High Order
40034 Energy Total Mode 2 – TonHr 0 – 65535 0 – 999 Read Only Low Order
40035 Energy Total Mode 2 – kTonHr 0 – 65535 0 – 65534 65535 Read Only High Order
40036 Energy Total Mode 1 – kWHr 0 – 65535 0 – 999 Read Only Low Order
40037 Energy Total Mode 1 – MWHr 0 – 65535 0 – 999 Read Only Middle Order
40038 Energy Total Mode 1 – GWHr 0 – 65535 0 – 65534 65535 Read Only High Order
40039 Energy Total Mode 2 – kWHr 0 – 65535 0 – 999 Read Only Low Order
40040 Energy Total Mode 2 – MWHr 0 – 65535 0 – 999 Read Only Middle Order
40041 Energy Total Mode 2 – GWHr 0 – 65535 0 – 65534 65535 Read Only High Order
40042 Volume Total Mode 1 - kGal 0 – 65535 0 – 999 Read Only Low Order
40043 Volume Total Mode 1 - MGal 0 – 65535 0 – 999 Read Only Middle Order
40044 Volume Total Mode 1 – GGal 0 – 65535 0 – 65534 65535 Read Only High Order
40045 Volume Total Mode 2 – kGal 0 – 65535 0 – 999 Read Only Low Order
40046 Volume Total Mode 2 – MGal 0 – 65535 0 – 999 Read Only Middle Order
40047 Volume Total Mode 2 – GGal 0 – 65535 0 – 65534 65535 Read Only High Order
40048 Volume Total Mode 1 – kLiters 0 – 65535 0 – 999 Read Only Low Order
40049
Volume Total Mode 1 – MLi-
ters
0 – 65535 0 – 999 Read Only Middle Order
40050 Volume Total Mode 1 – GLiters 0 – 65535 0 – 65534 65535 Read Only High Order
40051 Volume Total Mode 2 – kLiters 0 – 65535 0 – 999 Read Only Low Order
40052
Volume Total Mode 2 – MLi-
ters
0 – 65535 0 – 999 Read Only Middle Order
40053 Volume Total Mode 2 – GLiters 0 – 65535 0 – 65534 65535 Read Only High Order
40054 Volume Total Mode 1 –M³ 0 – 65535 0 – 999 Read Only Low Order
40055 Volume Total Mode 1 – kM³ 0 – 65535 0 – 65534 65535 Read Only High Order
40056 Volume Total Mode 2 –M³ 0 – 65535 0 – 999 Read Only Low Order
40057 Volume Total Mode 2 – kM³ 0 – 65535 0 – 65534 65535 Read Only High Order
40058 Mass Total – kLbs 0 – 65535 0 – 999 Read Only
Mass units are only
available when using
F-2000 Vortex Meter.
40059 Mass Total – MLbs 0 – 65535 0 – 65534 65535 Read Only
40060 Mass Total – Kkgs 0 – 65535 0 – 999 Read Only
40061 Mass Total – Mkgs 0 – 65535 0 – 65534 65535 Read Only
40062 Auxiliary Input Total (Di3) 0 – 65535 0 – 999 Read Only Low Order
40063 Auxiliary Input Total (x1000) 0 – 65535 0 – 65534 65535 Read Only High Order
40064 Zero Mode 1 Energy Total 0 – 1 0 – 1 N/A Read/Write
Write a value of 1 to
registers to reset totals.
Re-write a value of
zero to registers once
the totals reset.
40065 Zero Mode 1 Volume Total 0 – 1 0 – 1 N/A Read/Write
40066 Zero Mode 2 Energy Total 0 – 1 0 – 1 N/A Read/Write
40067 Zero Mode 2 Volume Total 0 – 1 0 – 1 N/A Read/Write
40068 Zero Auxiliary Input Total (Di3) 0 – 1 0 – 1 N/A Read/Write