System-10-P1 Manual 10/14 - 0656-9 / 18320 Page 6
GENERAL SPECIFICATIONS
CALIBRATION
Flow meter and temperature sensors are individually
calibrated, followed by a complete system calibration.
Field commissioning is also available.
ACCURACY
Differential temperature accuracy ±0.15° F over calibrated range
Computing nonlinearity within ±0.05%
TEMPERATURE SENSORS
Solid state sensors are custom calibrated using N.I.S.T.
traceable temperature standards.
Current based signal (mA) is unaffected by wire length.
PROGRAMMING
Factory programmed for specic application
MEMORY
Nonvolatile EEPROM memory retains all program
parameters and totalized values in the event of power loss.
DISPLAY
Alphanumeric LCD displays total energy, total ow,
energy rate, ow rate, supply temperature and return
temperature
Alpha: 16 character, 0.2” high
Numeric: 6 digit, 0.4” high
P1 OUTPUT POINTS
Name Point Type/
Category
Units
Total Energy 3/LAI BTU, kW-hrs or ton-hrs
Energy Rate 1/LAI BTU-hr, kW or tons
Total Flow 3/LAI gallons, liters or meters
3
Flow Rate 1/LAI gpm, gph, mgd, l/s, l/m, l/
hr or m
3
/hr
Supply Temperature 1/LAI °F or °C
Return Temperature 1/LAI °F or °C
Delta T 1/LAI °F or °C
Energy Total Reset 1/LDO Not applicable
Flow Total Reset 1/LDO Not applicable
Auxilliary Input 1 3/LAI Pulse Accumulator
Auxilliary Input Reset 1/LDO Not applicable
ADDITIONAL OUTPUT SIGNALS
Standard: Isolated solid-state dry contacts for energy total
Maximum contact ratings: 100 mA, 50VDC
Contact duration: 0.5, 1, 2 or 6 seconds
(factory selectable)
Optional: Multiple isolated analog outputs for energy rate,
ow rate, supply and return temperatures and delta T
(factory selectable)
Output type: 4-20mA, 0-10 volt or 0-5 volt
(eld selectable)
Optional Interval Data Logging:
This option provides up to 24 hours of rate and
total data logging in 15 minute intervals. Data
includes date/time stamp, measured value &
scaling factors when appropriate.
LIQUID FLOW SIGNAL INPUT
0-15 V pulse output from any ONICON ow meter
TEMPERATURE RANGE
Liquid temperature range: 32° F to 200° F
Optional extended temperature range available.
Ambient temperature range: -20° F to 140° F
MAINTENANCE
ONICON recommends periodic inspection and recalibration
for sensors connected to the System-10 BTU Meter. No other
periodic maintenance is required for the main unit.
MECHANICAL
ELECTRONICS ENCLOSURE:
Standard: Steel NEMA 13, wall mount, 8”x10”x4”
TEMPERATURE SENSOR THERMOWELLS:
Standard: ½” NPT brass thermowells (length varies with
pipe size) with junction box
Note: 6” pipes and larger require SS thermowell option
Optional:
• ½” NPT stainless steel thermowells
• Outdoor junction box with thermal isolation
• Hot tap thermowells for installations in a pressurized
system with no shutdown
ELECTRICAL
This equipment is intended for INSTALLATION CATEGORY
(OVERVOLTAGE CATEGORY) II applications.
INPUT POWER:
Factory Selectable:
24 ±4 VAC 50/60 Hz, 500 mA
120 VAC 50/60 Hz, 250 mA
230 VAC 50 Hz, 250 mA
INTERNAL FUSE RATINGS:
24 VAC - 1 Amp Slo-Blo, 3AG Fuse
120 VAC - 1/4 Amp Slo-Blo, 3AG Fuse
230 VAC - 1/8 Amp Slo-Blo, 3AG Fuse
OUTPUT:
24 VDC, 250 mA maximum
OVERCURRENT PROTECTIVE DEVICE RATINGS:
Supply mains overcurrent protective devices with the
following ratings:
120 VAC 50/60 Hz – 15 A
230 VAC 50 Hz – 6 A
WIRING:
Temperature signals: Use 18-22 ga twisted shielded pair
Flow signals: Use 18-22 ga shielded cable – see Flow Meter
Specication Sheet or Owner’s Manual for ONICON
Insertion Turbine Flow Meter for the correct number of
conductors
24 ±4 VAC input power: Use PVC jacketed copper cable with
a wire gauge suitable for the length of run and required
maximum current carrying capacity. The installation must
comply with all local, state and federal building codes.
120/230 VAC input power: Use a three wire service with one
wire protective earth ground. The installation must
comply with all local, state and federal building codes.
Note: Specications are subject to change without notice.