Onicon F-2600 Uživatelský manuál Strana 119

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 131
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 118
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204 Page A-7
Output Signals
(1)
Analog: volumetric meter-eld rangeable linear 4-20 mA output signal (1200
ohms maximum loop resistance) selected by user for mass ow rate or
volumetric ow rate.
Communications: HART, MODBUS-RTU, RS485, BACnet MS/TP
Multiparameter Meter: Up to three eld rangeable linear 4-20 mA output
signals (1200 ohms maximum loop resistance) selected from the ve
parameters mass ow rate, volumetric ow rate, temperature, pressure and
density.
Pulse: pulse output for totalization is a 50-millisecond duration pulse
operating a solid-state relay capable of switching 40 VDC, 40 mA maximum.
Note: (1) All outputs are optically isolated and require external power for
operation.
Alarms Up to three programmable solid-state relays for high, low or window alarms
capable of switching 40 VDC, 40 mA maximum.
Totalizer Based on user-determined ow units, six signicant gures in scientic
notation. Total stored in non-volatile memory.
Wetted Materials In-Line Flow Meter:
316L stainless steel standard
C276 hastelloy or A105 carbon steel optional
Insertion Flow Meter:
316L stainless steel standard
Teon® packing gland below 500° F (260° C)
Graphite packing gland above 500° F (260° C)
Enclosure Protection NEMA 4X and IP66 cast enclosure
Classication
Electrical Ports Two 3/4" female NPT ports
Mounting Connections In-Line: Wafer, 150, 300, 600 lb ANSI ange, PN16, PN40, PN64 ange
Insertion Hot Tap(1) Installation: 2" MNPT; 150, 300, 600 lb
ANSI ange, PN16, PN40, PN64 ange and optional retractor
with packing gland probe seal.
Note: (1) Removable under line pressure.
Mounting Position In-Line Flow Meter: No effect.
Insertion Flow Meter: Meter must be perpendicular within ± 5° of the pipe
centerline.
Certications Material Certicate – US Mill certs on all wetted parts
Pressure Test Certicate
Certicate of Conformance
NACE Certication (MR0175)
Oxygen Cleaning (CGA G-4.)
Zobrazit stránku 118