The oating point registers with values in display units are scaled to the same units as
are displayed, but are instantaneous values that are not smoothed. If display smoothing
is enabled (non-zero value entered in the Display TC item in the Display Menu), then the
register values will not agree exactly with the displayed values.
Exception Status Denitions
The Read Exception Status command (function code 07) returns the exception status byte,
which is dened as follows. This byte may be cleared by setting “coil” register #00003
(function code 5, address 2, data = 0xff00).
Bit(s) Denition
0-1 Byte order (see Modbus Order on page 2)
0 = 3-2:1-0 1 = 2-3:0-1
2 = 1-0:3-2 3 = 0-1:2-3
2 Temperature sensor fault
3 Pressure sensor fault
4 A/D converter fault
5 Period overow
6 Pulse overow
7 Conguration changed
Discrete Input Denitions
The status of the three alarms may be monitored via the Modbus Read Discrete Input
command (function code 02). The value returned indicates the state of the alarm, and will
be #1 only if the alarm is enabled and active. A zero value is transmitted for alarms that
are either disabled or inactive.
Registers Variable Function Code Address
10001 Alarm #1 state 02 0
10002 Alarm #2 state 02 1
10003 Alarm #3 state 02 2